10.2.8.3 JPDS Contact/Fuse

Variable**
DryCntStat_x_y
AuxFuseStat_x_y
** x = R, S, T and y = 1, 2

10.2.8.4 JPDG Inputs

Parameter
InputDiagEnable
PS28vEnable
DC_24v_Trig_Volt
Gnd_Mag_Trig_Volt
ACFdbkInVoltage
ACFdbkInTol
Variable
PS28vStat
DC_24VFdbkMag
DC_24VGnd_FdbkMag
AC_Fdbk1_Volt_1
AC_Fdbk1_Volt_2
316
GEH-6855_Vol_II
Description
Pbus x dry contact status (connector Jx)
Pbus x fuse status (connector JAx)
Description
DC or AC volt diagnostics enable
Applicable only to DC_24VFdbkMag, AC_Fdbk1_Volt_#
PS 28 V feedback enable;
Enable – Enables feedback
Disable – Disables feedback and diagnostics
NoDryCnt – Enables feedback, but disables dry contact
diagnostics
Applicable only to PS28vStat
DC 24 V fault trigger voltage
Applicable only to DC_24VFdbkMag
Ground magnitude fault trigger voltage
Applicable only to DC_24VGnd_FdbkMag
AC feedback input voltage
Applicable only to AC_Fdbk1_Volt_#
AC feedback tolerance
Applicable only to AC_Fdbk1_Volt_#
Description
Main JPDG - PS 28 V feedback from Pbus R input
JPDG - DC 24V/48 V magnitude
JPDG - ground feedback magnitude
Main JPDG - AC 115 to 250 V feedback input voltage
Main JPDG - AC 115 to 250 V feedback input voltage
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information
Direction
Type
Input
BOOL
Input
BOOL
Choices
Enable, Disable
Enable, Disable, NoDryCnt
10 to 60
1 to 30
100 to 250 V
0pct, 5pct, 10pct, 20pct
Direction
Type
AnalogInput
REAL
AnalogInput
REAL
AnalogInput
REAL
AnalogInput
REAL
AnalogInput
REAL