Trlys#F Specifications; Derating Voted Relay Contact Output Diagram - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

6.7.4 TRLYS#F Specifications

Item
Number of Output Relay Channels
Rated Voltage on Relays
Max Load Current
Max Response Time On
Contact Life
Fault Detection
Size
Operating Temperature
The following figure illustrates derating the voted contact output channel quantity based on the maximum applied ambient.
12
10
8
6
4
2
-40 -20
Temperature ºC
TRLY_#F with WDPF
12
10
8
6
4
2
-40 -20
YDOA Discrete Output Modules
TRLYS#F Specification
S1F: 12 NO contacts
S2F: 12 NC contacts
Nominal 100/125 V dc or 24 V dc
Nominal 115 V ac
0.5/0.3 A resistive for 100/125 V dc operation
5.0 A resistive for 24 V dc operation
5.0 A resistive for 115 V ac
25 ms
Electrical operations: 100,000
Coil Voltage disagreement with command
Unplugged cable or loss of communication with I/O pack; relays de-energize if
communication with associated I/O pack is lost
17.8 cm wide x 33.02 cm high (7.0 in x 13.0 in)
Refer to the following figure, Derating Voted Relay Contact Output Diagram.
TRLY_#F
0 20 40 60 80
0 20 40 60 80
Temperature ºC

Derating Voted Relay Contact Output Diagram

Public Information
TRLY_#F
12
Not applicable with
10
ambient above
8
60ºC (140 ºF)
6
Maximum number of
4
Kn connecting to odd
2
or even outputs
-40 -20
0 20 40 60 80
Temperature ºC
Odd outputs - K1, 3, 5, 7, 9, 11
Even outputs - K2, 4, 6, 8,10, 12
TRLY_#F with WDPF
8
Not applicable with
ambient above 55ºC (131 ºF)
7
6
5
4
3
Maximum number of Kn
2
1
-40 . . . . .
55 60
Temperature ºC
5 outputs - K1, 6, 7, 12, (K3 or K10)
4 outputs - K1, 6, 7, 12
GEH-6855_Vol_II System Guide 159
70
80

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents