491
Description Hardware watchdog has been disabled
Possible Cause
•
A runtime malfunction has disabled the hardware watchdog protective function.
•
A hardware failure has disabled the hardware watchdog protective function.
Solution
•
Reload the firmware and restart the I/O pack or module.
•
If the problem persists, replace the I/O pack or module or the controller.
499
Description I/O pack is connected to an unknown board
Possible Cause
•
The terminal board or auxiliary terminal board connected to the I/O pack or module is not recognized by this version of
firmware.
•
This can occur if a new terminal board has been connected but the I/O pack is configured with firmware that does not
support the new hardware.
Solution
•
Upgrade the ControlST software suite to a version that supports the new hardware.
•
Download latest firmware and parameters to the I/O pack or module.
500
Description
I/O pack is connected to the wrong terminal board
Possible Cause
The I/O pack or module is connected to a recognized terminal board that is not supported.
Solution
•
Refer to one of the following system guides for a list of supported hardware combinations: GEH-6721_Vol_II,
GEH-6855_Vol_II, GEH-6800, or GEH-6779. From the Start menu, select All Programs, GE ControlST,
Documentation.
•
Verify that the I/O pack is connected to a terminal board that is supported.
•
Replace the I/O pack or terminal board to create a supported combination.
•
Use the ToolboxST application to reconfigure the I/O module.