Jpdc-P28V-T Contact Input (Jt Connector) Indicates Ps Problem; Ppda Invalid Combination: More Than 1 Jpdc Board Present; Ppda Invalid Combination: Jpdc And Jpds Boards Present Together - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

189
Description JPDC-P28v-T contact input (JT connector) indicates PS problem.
Possible Cause
The power supply contact is open. The power supply is not operating normally.
The power supply contact feedback is not connected to the specified terminal board connector.
The power supply dry contact is not used.
Solution
Verify the status of the power supply contact, and that the power supply is operating correctly.
Verify the connections between the power supply and the specified connector on the JPDC.
The input is not used. Set PS28vEnable to Disable.
The power supply is used, but the dry contact feedback is not connected. Set PS28vEnable to NoDryCnt to disable this
alarm, but continue to monitor the 28 V power supply input.
190
Description PPDA Invalid Combination: More than 1 JPDC board present.
Possible Cause The PPDA allows only one JPDC board to be connected as part of the Power Distribution module. The
PPDA has detected more than one JPDC boards connected through the ribbon cables to the PDM.
Solution
Verify that only one JPDC terminal boards is connected to the PPDA. The PPDA should be plugged into the JPDC
terminal board.
Reboot the PPDA after the hardware connections are corrected.
191
Description PPDA Invalid Combination: JPDC and JPDS boards present Together.
Possible Cause The PPDA does not allow JPDC and JPDS terminal boards to be mixed. The PPDA has detected both
JPDC and JPDS terminal boards connected through ribbon cables to the PDM.
Solution
Verify that there are only JPDC or JPDS boards present, but not both.
Verify that the ToolboxST configuration matches the hardware configuration.
Reboot the PPDA after the hardware connections are corrected.
354
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents