2.1.5 UCSC Operation

2.1.5.1 UDH Network Configuration

The UCSC is typically set up for communications on the UDH network using an unencrypted minimum 4 GB flash drive that
is configured with the ToolboxST application. The factory default IP address is 192.168.101.111. The correct UDH IP address
must be properly set up so that the controller can communicate to the site HMIs.
Note The UCSC, as shipped from the factory, does not include the software on the controller to support communication
from the PHY PRES button to the EFA. The user needs to download to the controller at least once (using ToolboxST) to
enable this.
➢ ➢ To change the UDH network IP address for the UCSC
1.
Verify that the HMI computer running the ToolboxST application has been configured (through Windows OS) with the
correct IP address for the UDH network.
From the ToolboxST Component Editor, verify that the controller Platform is set as UCSCxxx.
2.
From the Component Editor General tab Property Editor Network Adapter 0, configure the appropriate controller IP
3.
address as a relative subnet to the HMI's UDH IP address from Step 1.
Insert a non-encrypted, USB 2.0 only flash drive with a minimum 4 GB capacity into a USB port of the computer that is
4.
running the ToolboxST application.
From the ToolboxST Component Editor, select Device, Download, and Controller Setup to launch the Controller
5.
Setup Wizard.
Follow the on-screen instructions to load the flash drive. Refer to the ToolboxST User Guide for Mark VIeS Functional
6.
Safety Systems (GEH-6862), the section Configure and Transfer IP Address to UCSC Controller for further instructions.
➢ ➢ To set the controller's network address using the COM port
Attention
1.
Connect the UCSC COM port adapter to the Ethernet cable and the other end of the cable to the UCSC COM port.
2.
Connect the UCSC COM port adapter to the serial to USB cable, then to the computer that runs the ToolboxST
application.
From the ToolboxST Component Editor General tab, select Device, Download, and Controller Setup to launch the
3.
Controller Setup Wizard.
Follow the on-screen instructions to transfer the UDH network address to the controller. Refer to the ToolboxST User
4.
Guide for Mark VIeS Functional Safety Systems (GEH-6862), the section Configure and Transfer IP Address to UCSC
Controller for further instructions.
Controllers
Use a UCSC COM port adapter, a standard serial to USB cable, and/or a Cat5e or
better Ethernet cable for this connection.