Waiting On Ip Addr Ionet Before Continuing; Iopack - The Fpga Is Not Generating An I/O Interrupt - GE Mark VIeS System Manual

Functional safety systems for general market
Hide thumbs Also See for Mark VIeS:
Table of Contents

Advertisement

293
Description
Waiting on IP addr Ionet [ ] before continuing
Possible Cause
I/O pack or module waiting to obtain network address from the controller using DHCP
Network problem
Controller problem
I/O pack or module not configured correctly, or incorrect ID (barcode)
I/O pack or module is configured with 2 network addresses in the ToolboxST application, but only has one network
physically connected.
Solution
Verify that the controller is online.
Confirm that the correct terminal board ID is present in the ToolboxST configuration.
Check IONet (switches, cables).
From the ToolboxST application, verify that the I/O pack or module network configuration matches the physical network
configuration.
295
Description

IOPACK - The FPGA is not generating an I/O interrupt

Possible Cause
There is a FPGA inside the I/O pack or module that controls I/O or module hardware. The logic in the
FPGA generates an interrupt to the processor requesting that the I/O or module be serviced. That interrupt is not occurring as
expected.
Solution
Rebuild system and download to the I/O pack or module. If the problem persists, replace the I/O pack.
300
Description
Application Code Load Failure
Possible Cause
During commissioning or maintenance:
Invalid application configuration
During normal operation:
There is a firmware or hardware malfunction
Solution
Rebuild and download the application to all processors.
Reload the firmware and application.
If the problem persists, replace processor module.
462
GEH-6855_Vol_II
GEH-6855_Vol_II Mark VIeS Functional Safety Systems Volume II
Public Information