Series start-up
6.3 Importing data
9. The storage directory, e.g.: on the card: user/sinumerik/data/archive and the file, e.g.
"PLC.ARC" are displayed. Press the "OK" softkey.
10. Now, you can assign a different name.
11. Press "OK" again to start the data transmission.
Note
When the drive data is selected, it takes 1 to 2 minutes after pressing the "Create
archive" softkey until the drive has saved the data on the CompactFlash Card.
Note
When you save very large files to the CompactFlash card, the message "Please wait - file
being flashed" appears. Acknowledge the message with the "Recall" button.
6.3
Importing data
To import the backed up data to another control, proceed as follows:
Procedure
1. In the "Services" area, select the created archive (arc.) and press the "Read in archive"
vertical softkey. The "Read in update archive" window pane opens.
2. Press the "OK" softkey to start importing.
3. Press the " ˆ " key to return to the previous window.
4. After importing an NC series commissioning archive you must restart HMI-Embedded.
5. Press the "NCK Reset" vertical softkey in the "Commissioning" operating area. NCK and
drive are restarted.
Or press the CRT and Q keys and then Enter.
Protocol
Press the "Log" softkey to view the transmission report on the screen.
98
Commissioning HMI-Embedded (IM2)
Commissioning Manual, 01/2008, 6FC5397-8CP10-1BA0