Section 4
Protection functions
662
The operation of LREFPNDF can be described using a module diagram. All the
modules in the diagram are explained in the next sections.
I_A
I_B
I3P
I_C
Io
IRES
BLOCK
GUID-CFC6C9E6-AC71-460E-8175-46FEDDB86D7A V1 EN
Figure 363:
Functional module diagram
Earth-fault detector
The operation is based on comparing the amplitude and the phase difference between
the sum of the fundamental frequency component of the phase currents (ΣI, residual
current) and the fundamental frequency component of the neutral current (Io) flowing
in the conductor between the transformer or generator's neutral point and earth. The
differential current is calculated as the absolute value of the difference between the
residual current, that is, the sum of the fundamental frequency components of the
phase currents I_A, I_B and I_C, and the neutral current. The directional differential
current ID_COSPHI is the product of the differential current and cosφ. The value is
available in the monitored data view.
ID COSPHI
_
(
I Io
) cos
=
Σ
GUID-C658A372-E0AE-4E0C-8C18-602106E663E9 V1 EN
ΣI
GUID-9CF699E3-DCA0-4618-90F7-8052C127E1AF V1 EN
ϕ
GUID-F60A9116-3493-4594-A695-D57B0B7F4228 V1 EN
Io
GUID-1AA9F188-BEF1-49C1-99D5-28CDC602EE41 V1 EN
An earth fault occurring in the protected area, that is, between the phase CTs and the
neutral connection CT, causes a differential current. The directions, that is, the phase
difference of the residual current and the neutral current, are considered in the
operation criteria to maintain selectivity. A correct value for CT connection type is
determined by the connection polarities of the current transformer.
The current transformer ratio mismatch between the phase current
transformer and neutral current transformer (residual current in the
Timer
Earth fault
t
detector
Second
harmonic
blocking
ϕ
Residual current
Phase difference between the residual and neutral currents
Neutral current
1MRS759142 C
OPERATE
START
BLK2H
(Equation 124)
Technical Manual
REX640