1MRS759142 C
3.17.3.5
REX640
Technical Manual
In this case, ROVPTOV1 and ROVPTOV2 in
reference level in their settings. URES_CLC and URES_MEAS in
to the same level.
UTVTR1[1]_URES_CLC
UTVTR1[1]_URES_MEAS
GUID-9DCCDA72-D3EF-4BFF-B37E-41234E7D4140 V1 EN
Figure 74:
Two ROVPTOV instances, one using calculated U
measured U

Signals

Table 128:
UTVTR Input signals
Name
Type
UL1
SIGNAL
UL2
SIGNAL
UL3
SIGNAL
URES
SIGNAL
MINCB_OPEN
BOOLEAN
Table 129:
UTVTR Output signals
Name
Type
ALARM
BOOLEAN
WARNING
BOOLEAN
URES_ALARM
BOOLEAN
URES_WARNING
BOOLEAN
U3P
SIGNAL
URES_CLC
SIGNAL
URES_MEAS
SIGNAL
URES_CLC_DR
SIGNAL
URES_MEAS_DR
SIGNAL
U1_DR
SIGNAL
U2_DR
SIGNAL
U3_DR
SIGNAL
Table continues on next page
Figure 74
ROVPTOV1
URES
OPERATE
BLOCK
START
O:12|T:5|I:1
ROVPTOV2
URES
OPERATE
BLOCK
START
O:13|T:5|I:2
0
Default
Description
-
Analog input
-
Analog input
-
Analog input
-
Residual voltage
0=False
Active when external MCB opens protected voltage
circuit
Description
Alarm
Warning
Alarm
Warning
Three-phase voltages
Residual voltage, calculated
Residual voltage, measured
Residual voltage, calculated, for disturbance
recorder
Residual voltage, measured, for disturbance
recorder
Phase voltage U1 for disturbance recorder
Phase voltage U2 for disturbance recorder
Phase voltage U3 for disturbance recorder
Section 3
Basic functions
can both use the same U
Figure 73
are scaled
ROVPTOV1[1]_OPERATE
ROVPTOV2[2]_OPERATE
and the other
0
0
191