ABB RELION REX640 Technical Manual page 181

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
Parameter
Values (Range)
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Value low low limit
-10000.0...10000.0
Value deadband
100...100000
Table 103:
Input-specific settings for RTD1...10
Parameter
Values (Range)
Input mode
1=Not in use
2=Resistance
10=Pt100
11=Pt250
20=Ni100
21=Ni120
22=Ni250
30=Cu10
Input maximum
0...4000
Input minimum
0...4000
Value unit
1=Dimensionless
5=Ampere
23=Degrees celsius
30=Ohm
Value maximum
-10000.0...10000.0
Value minimum
-10000.0...10000.0
Val high high limit
-10000.0...10000.0
Value high limit
-10000.0...10000.0
Value low limit
-10000.0...10000.0
Table continues on next page
REX640
Technical Manual
Unit
Step
Unit
Step
Section 3
Basic functions
Default
Description
10000
Output value high
warning limit for
supervision
-10000
Output value low
warning limit for
supervision
-10000
Output value low
alarm limit for
supervision
1000
Deadband
configuration value
for integral
calculation.
(percentage of
difference between
min and max as
0,001 % s)
Default
Description
1=Not in use
Analog input mode
4000
Maximum analog
input value for mA or
resistance scaling
0
Minimum analog
input value for mA or
resistance scaling
1=Dimensionless
Selected unit for
output value format
10000
Maximum output
value for scaling and
supervision
-10000
Minimum output
value for scaling and
supervision
10000
Output value high
alarm limit for
supervision
10000
Output value high
warning limit for
supervision
-10000
Output value low
warning limit for
supervision
175