Function Block; Functionality; Analog Channel Configuration - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
4.2.6.2
4.2.6.3
4.2.6.4
488

Function block

GUID-6A982B06-C7DE-4123-AF18-1A6F6927ED4C V1 EN
Figure 267:
Function block

Functionality

The harmonics-based earth-fault protection function HAEFPTOC is used instead of a
traditional earth-fault protection in networks where a fundamental frequency
component of the earth-fault current is low due to compensation.
By default, HAEFPTOC is used as a standalone mode. Substation-wide application
can be achieved using horizontal communication where the detection of a faulty
feeder is done by comparing the harmonics earth-fault current measurements.
The function starts when the harmonics content of the earth-fault current exceeds the
set limit. The operation time characteristic is either definite time (DT) or inverse
definite minimum time (IDMT). If the horizontal communication is used for the
exchange of current values between the protection relays, the function operates
according to the DT characteristic.
The function contains a blocking functionality. It is possible to block function outputs,
timer or the function itself.

Analog channel configuration

HAEFPTOC has one analog group input which must be properly configured.
Table 529:
Analog signals
Input
IRES
See the preprocessing function blocks in this document for the
possible signal sources.
Improper analog channel configuration causes a validation error if the analog
channels are not completely configured or they do not match with certain settings. For
troubleshooting, check the contents of this chapter and also the preprocessing blocks
in this document. The configuration can be written to the protection relay once the
mismatch is corrected.
Description
Residual current (measured or calculated)
1MRS759142 C
REX640
Technical Manual