Figure 503:
Example of out of step detection
The shaded region indicates a fault zone in a distance protection function. For curve
A, the impedance moves into the out of step zone and leaves slowly, indicating the
occurrence of a swing that quickly stabilizes. For curve B, the impedance moves
slowly into the out of step zone and exits the zone indicating that the network is
becoming unstable. For curve C, impedance rapidly moves into, and remains in, the
fault zone indicating an actual fault and not an out of step condition.

Signals

Table 858:
OOSRPSB Input signals
Name
Type
I3P
SIGNAL
U3P
SIGNAL
BLOCK
BOOLEAN
DISABLE
BOOLEAN
Table 859:
OOSRPSB Output signals
Name
Type
OPERATE
BOOLEAN
SWING
BOOLEAN
OSB
BOOLEAN
OSB_Z2
BOOLEAN
SWING_OP
BOOLEAN
X
C
-X
Default
Description
-
Three-phase currents
-
Three-phase voltages
0=False
Block signal for activating the blocking mode
0=False
Disable input
Description
Out of step operate on zone 1 or zone 2
Swing condition detected
Out of step block for zone 1
Out of step block for zone 2
Out of step operate on zone 3
Section 4
Protection functions
A
R
929