Signals - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

1MRS759142 C
4.10.7
REX640
Technical Manual
n
specified maximum allowed number of motor start-ups
t
start-up time of the motor (in seconds)
margin safety margin (~10...20 percent)
Counter Red rate
Setting of
Counter Red rate is calculated by
t
t
=
s
t
reset
GUID-30D5BCC8-06EE-4101-89F5-BF2762567C6A V1 EN
t
specified start time of the motor in seconds
t
duration during which the maximum number of motor start-ups stated by the manufacturer can be
reset
made; time in hours

Signals

Table 934:
STTPMSU Input signals
Name
Type
I3P
SIGNAL
BLOCK
BOOLEAN
BLK_LK_ST
BOOLEAN
CB_CLOSED
BOOLEAN
STALL_IND
BOOLEAN
ST_EMERG_ENA
BOOLEAN
Table 935:
STTPMSU Output signals
Name
Type
OPR_IIT
BOOLEAN
OPR_STALL
BOOLEAN
MOT_START
BOOLEAN
LOCK_START
BOOLEAN
Protection functions
Default
Description
-
Three-phase currents
0=False
Block of function
0=False
Blocks lock out condition for restart of motor
0=False
Input showing the status of motor circuit breaker
0=False
Input signal for showing the motor is not stalling
0=False
Enable emergency start to disable lock of start of
motor
Description
Operate/trip signal for thermal stress.
Operate/trip signal for stalling protection.
Signal to show that motor startup is in progress
Lock out condition for restart of motor.
Section 4
(Equation 239)
1003