Communication logic for residual overcurrent
RESCPSCH
Identification
Function description
Communication logic for residual
overcurrent
Function block
GUID-61E9C294-8F58-44C7-ABC8-D9080F9F5215 V1 EN
Figure 622:
Function block
Functionality
The communication logic for residual overcurrent function RESCPSCH is used to
achieve instantaneous fault clearing independent of the fault location on the protected
feeder. There are four available communication scheme types.
Direct underreaching transfer trip DUTT
Permissive underreaching transfer trip PUTT
Permissive overreaching transfer trip POTT
Directional comparison blocking scheme DCB
The directional comparison unblocking scheme DCUB can also be provided by
complementing the permissive schemes with an additional logic called the unblocking
function, which is also included in RESCPSCH.
If the permissive overreaching scheme is used, some of the power system conditions
require additional special logic circuits, such as the current reversal and weak-end
infeed logic for residual overcurrent function RCRWPSCH.
IEC 61850
IEC 60617
identification
identification
RESCPSCH
CLN
1MRS759142 C
ANSI/IEEE C37.2
device number
85 67G/N
SCHLGC
REX640
Technical Manual