Section 4
Protection functions
726
GUID-CF8466CA-3596-4DF6-AE35-2BDB60E1FD1C V1 EN
Figure 404:
High-impedance differential protection with different CT burden value
on each branch
The stabilizing voltage, that is the voltage appearing across the measuring branch
during an out-of-zone fault, is calculated assuming that one of the CTs connected in
parallel is fully saturated. The stabilizing voltage can be calculated using
166.
I
k
max
U
R
R
(
)
=
+
s
in
m
n
GUID-2CF2ADDE-5E7E-46AA-AF77-274E3114D332 V1 EN
I
The highest through-fault current in primary Amps. The highest earth fault or short circuit current
kmax
during out-of-zone fault
n
The turns ratio of the CT
R
The secondary winding resistance of CT in ohms
in
R
The resistance (maximum of R
m
The current transformers must be able to force enough current to operate the relay
through the differential circuit during a fault condition inside the protection zone. To
ensure this, the knee point voltage U
stabilizing voltage U
.
s
The required knee point voltage U
Equation
167.
+ R
) of the CT secondary circuit in ohms
in
m
should be at least twice higher than the
kn
of the current transformer is calculated using
kn
1MRS759142 C
Equation
(Equation 166)
REX640
Technical Manual