Monitored Data - ABB RELION REX640 Technical Manual

Hide thumbs Also See for RELION REX640:
Table of Contents

Advertisement

Section 4
Protection functions
Parameter
Power start value
Reference power
Characteristic angle
Time multiplier
Operating curve type
Operate delay time
Table 544:
WPWDE Non group settings (Basic)
Parameter
Operation
Table 545:
WPWDE Non group settings (Advanced)
Parameter
Measurement mode
Correction angle
Min operate current
Min operate voltage
Reset delay time
Pol reversal
4.2.7.11
508
Values (Range)
Unit
0.003...1.000
xSn
0.050...1.000
xSn
-179...180
deg
0.025...2.000
5=ANSI Def. Time
15=IEC Def. Time
20=Wattmetric
IDMT
60...300000
ms
Values (Range)
Unit
1=on
5=off
Values (Range)
Unit
1=RMS
2=DFT
3=Peak-to-Peak
0.0...10.0
deg
0.010...1.000
xIn
0.01...1.00
xUn
0...60000
ms
0=False
1=True

Monitored data

Table 546:
WPWDE Monitored data
Name
FAULT_DIR
START_DUR
DIRECTION
ANGLE
Table continues on next page
Step
Default
0.001
0.003
0.001
0.150
1
-90
0.005
1.000
15=IEC Def. Time
10
60
Step
Default
1=on
Step
Default
2=DFT
0.1
2.0
0.001
0.010
0.01
0.01
1
20
0=False
Type
Values (Range)
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
0.00...100.00
Enum
0=unknown
1=forward
2=backward
3=both
FLOAT32
-180.00...180.00
1MRS759142 C
Description
Start value for residual active power
Reference value of residual power for
Wattmetric IDMT curves
Characteristic angle
Time multiplier for Wattmetric IDMT
curves
Selection of time delay curve type
Operate delay time for definite time
Description
Operation Off / On
Description
Selects used current measurement mode
Angle correction
Minimum operating current
Minimum operating voltage
Reset delay time
Rotate polarizing quantity
Unit
Description
Detected fault direction
%
Ratio of start time /
operate time
Direction information
deg
Angle between polarizing
and operating quantity
Technical Manual
REX640