Table 19:
Secondary IP address parameters
Parameter
Configuration/Communication/
Ethernet/Network 2 address/
Enable
Configuration/Communication/
Ethernet/Network 2 address/IP
address
Configuration/Communication/
Ethernet/Network 2 address/IP
address
Configuration/Communication/
Ethernet/Network 2
address/MAC address
The IP address for Network 2 is disabled by default settings, and all Ethernet ports are
assigned to the same IP address used in the Network 1 address menu Configuration/
Communication/Ethernet/Network 1. If Network 2 is taken into use by the setting
Enable="True" (requires reboot), the interlink port X3 of the COM module is assigned
to this second network, using the IP address and subnet parameters in the Network 2
address menu Configuration/Communication/Ethernet/Network 2 address.
If the Network 2 interface is enabled, PTP time synchronization and
SMV/GOOSE multicast are disabled for that port.
The secondary IP setting must not collide with the primary Network 1
IP address or LHMI IP address 192.168.0.x, otherwise the secondary
IP address is not taken into use.
Options
False (default)
TRUE
0.0.0.0
0.0.0.0
xx-xx-xx-xx-xx-xx
Section 3
Basic functions
Description
Network 2 disabled
Network 2 enabled
IP address for Network 2
Subnet address for Network 2
MAC address for Network 2