Ap-23 No-Flow Function; Ap-24 No-Flow Delay; Ap-26 Dry Pump Function; Ap-40 Minimum Run Time - GE AF-600 FP Operating Instructions Manual

Fan and pump drive (460v/575v 150hp and above)
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

AP-23 No-Flow Function

Option:
[0] *
Off
[1]
Sleep Mode
[2]
Warning
[3]
Alarm

AP-24 No-Flow Delay

Range:
10 s*
[1 - 600 s]

AP-26 Dry Pump Function

Option:
7
[0] *
Off
[1]
Warning
[2]
Alarm

AP-40 Minimum Run Time

Range:
10 s*
[0 - 600 s]
AP-41 Minimum Sleep Time
Range:
10 s*
[0 - 600 s]
AP-42 Wake-up Speed [RPM]
Range:
0 RPM*
[par. F-18 - par. F-17 RPM]
AP-60 Broken Belt Function
Option:
[0] *
Off
[1]
Warning
[2]
Trip
AP-61 Broken Belt Torque
Range:
10 %*
[0 - 100 %]
96
Function:
Common actions for Low Power Detection and Low Speed Detection (Individual selections not possible).
Messages in the keypad display (if mounted) and/or signal via a relay or a digital output.
The frequency converter trips and motor stays stopped until reset.
Function:
Set the time Low Power/Low Speed must stay detected to activate signal for actions. If detection disap-
pears before run out of the timer, the timer will be reset.
Function:
Low Power Detection must be Enabled (par. AP-21 Low Power Detection) and commissioned (using either
par. AP-3#, No Flow Power Tuning, or par. AP-20 Low Power Auto Set-up) in order to use Dry Pump De-
tection.
Messages in the keypad display (if mounted) and/or signal via a relay or a digital output.
The frequency converter trips and motor stays stopped until reset.
Function:
Set the desired minimum running time for the motor after a start command (digital input or Bus) before
entering Sleep Mode.
Function:
Set the desired Minimum Time for staying in Sleep Mode. This will override any wake up conditions.
Function:
To be used if par. K-02 Motor Speed Unit has been set for RPM (parameter not visible if Hz selected). Only
to be used if par. H-40 Configuration Mode is set for Open Loop and speed reference is applied by an
external controller.
Set the reference speed at which the Sleep Mode should be cancelled.
Function:
Selects the action to be performed if the Broken Belt condition is detected
Function:
Sets the broken belt torque as a percentage of the rated motor torque.
AF-600 FP High Power Operating Instructions

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents