Shielded Cables; Motor Cable - GE AF-600 FP Operating Instructions Manual

Fan and pump drive (460v/575v 150hp and above)
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Unit Size
41, 42, 43 and 44
51 and 52
61, 62, 63 and 64
Table 3.1: Torque for terminals

3.1.6 Shielded Cables

It is important that shielded and armoured cables are connected in a proper way to ensure high EMC immunity and low emissions.
Connection can be made using either cable glands or clamps:
EMC cable glands: Generally available cable glands can be used to ensure an optimum EMC connection.
EMC cable clamp: Clamps allowing easy connection are supplied with the frequency converter.

3.1.7 Motor cable

The motor must be connected to terminals U/T1/96, V/T2/97, W/T3/98. Earth to terminal 99. All types of three-phase asynchronous standard motors can be used
with a frequency converter unit. The factory setting is for clockwise rotation with the frequency converter output connected as follows:
Terminal No.
96, 97, 98, 99
• Terminal U/T1/96 connected to U-phase
• Terminal V/T2/97 connected to V-phase
• Terminal W/T3/98 connected to W-phase
The direction of rotation can be changed by switching two phases in the motor cable or by changing the setting of par. H-08 Reverse Lock.
Motor rotation check can be performed using par. P-08 Motor Rotation Check and following the steps shown in the display.
Terminal
Mains
Motor
Load sharing
Brake
Mains
Motor
Load sharing
Brake
Mains
Motor
Load sharing
Brake
Regen
Function
Mains U/T1, V/T2, W/T3
Earth
AF-600 FP High Power Operating Instructions
Torque
19 Nm (168 in-lbs)
9.5 (84 in-lbs)
19 NM (168 in-lbs)
9.5 (84 in-lbs)
19 Nm (168 in-lbs)
19 Nm (168 in-lbs)
9.5 Nm (84 in-lbs)
19 Nm (168 in-lbs)
Bolt size
M10
M8
M10
M8
M10
M10
M8
M10
3
21