Data transfer from Keypad to Frequency converter:
1.
Go to par. K-50 Keypad Copy
2.
Press the [OK] key
3.
Select "All from Keypad"
4.
Press the [OK] key
The parameter settings stored in the GLCP are now transferred to the frequency converter indicated by the progress bar. When 100% is reached, press [OK].

6.1.8 Restore Factory Settings

There are two ways to restore the drive to factory settings: Recommended restore and manual restore.
Please be aware that they have different impact according to the below description.
Recommended restore (via par. H-03 Restore Factory Settings)
1.
Select par. H-03 Restore Factory Settings
2.
Press [OK]
3.
Select [2] Restore Factory Settings
4.
Press [OK]
5.
Remove power to unit and wait for display to turn off.
6.
Reconnect power and the frequency converter is reset. Note that
first start-up takes a few more seconds.
7.
Press [Reset]

Manual restore

NB!
When carrying out manual initialisation, serial communication, RFI filter settings and fault log settings are reset.
1. Disconnect from mains and wait until the display turns off.
2a. Press [Status] - [Main Menu] - [OK] at the same time while power
up for keypad.
3. Release the keys after 5 s.
4. The frequency converter is now programmed according to de-
fault settings.
AF-600 FP High Power Operating Instructions
par. H-03 Restore Factory Settings restores all except:
par. SP-50 RFI Filter
par. O-30 Protocol
par. O-31 Address
par. O-32 Drive Port Baud Rate
par. O-35 Minimum Response Delay
par. O-36 Max Response Delay
par. O-37 Maximum Inter-Char Delay
par. ID-00 Operating Hours to par. ID-05 Over Volt's
par. ID-20 Historic Log: Event to par. ID-22 Historic Log: Time
par. ID-30 Alarm Log: Error Code to par. ID-32 Alarm Log: Time
The Manual Restore restores all except:
par. ID-00 Operating Hours
par. ID-03 Power Up's
par. ID-04 Over Temp's
par. ID-05 Over Volt's
6
79