NB!
External stop signals activated by means of control signals or a serial bus will override a "start" command via the Keypad.
[Off]
The [Off] key stops the connected motor. The key can be selected as Enable [1] or Disable [0] via par. K-41 [Off] Button on Keypad. If no external stop function is
selected and the [Off] key is inactive the motor can only be stopped by disconnecting the mains supply.
[Auto ]
The [Auto ] key enables the frequency converter to be controlled via the control terminals and/or serial communication. When a start signal is applied on the
control terminals and/or the bus, the frequency converter will start. The key can be selected as Enable [1] or Disable [0] via par. K-42 [Auto] Button on Keypad.
[Reset]
The [Reset] key is used for resetting the frequency converter after an alarm (trip). It can be selected as Enable [1] or Disable [0] via par. K-43 [Reset] Button on
Keypad.
The parameter shortcut can be carried out by holding down the [Main Menu] key for 3 seconds. The parameter shortcut allows direct access to any parameter.
6

6.1.3 RS-485 Bus Connection

One or more frequency converters can be connected to a controller (or mas-
ter) using the RS-485 standard interface. Terminal 68 is connected to the P
signal (TX+, RX+), while terminal 69 is connected to the N signal (TX-,RX-).
If more than one frequency converter is connected to a master, use parallel
connections.
In order to avoid potential equalizing currents in the screen, earth the cable screen via terminal 61, which is connected to the frame via an RC-link.

Bus termination

The RS-485 bus must be terminated by a resistor network at both ends. If the drive is the first or the last device in the RS-485 loop, set the switch S801 on the
control card for ON.
For more information, see the paragraph Switches S201, S202, and S801.

6.1.4 How to Connect a PC to the frequency converter

To control or program the frequency converter from a PC, install the PC-based Drive Control Tool DCT 10..
The PC is connected via a standard (host/device) USB cable, or via the RS-485 interface as shown in the AF-600 FP Design Guide, chapter How to Install > Installation
of misc. connections.
NB!
The USB connection is galvanically isolated from the supply voltage (PELV) and other high-voltage terminals. The USB connection is connected to protection
earth on the frequency converter. Use only isolated laptop as PC connection to the USB connector on the frequency converter.
76
AF-600 FP High Power Operating Instructions
Illustration 6.6: Connection example.