F-12 Motor Thermistor Input

Option:
[0] *
None
[1]
Analog input 53
[2]
Analog input 54
[3]
Digital input 18
[4]
Digital input 19
[5]
Digital input 32
[6]
Digital input 33
NB!
This parameter cannot be adjusted while the motor is running.
NB!
Digital inputs should be set to "No operation" - see par. E-##.

F-24 Holding Time

Range:
0.0 s*
[0.0 - 120.0 s]

F-26 Motor Noise (Carrier Freq)

Option:
[0]
1.0 kHz
[1]
1.5 kHz
[2]
2.0 kHz
[3]
2.5 kHz
[4]
3.0 kHz
[5]
3.5 kHz
[6]
4.0 kHz
[7] *
5.0 kHz
[8]
6.0 kHz
[9]
7.0 kHz
[10]
8.0 kHz
[11]
10.0 kHz
[12]
12.0 kHz
[13]
14.0 kHz
[14]
16.0 kHz
Function:
Select the input to which the thermistor (PTC sensor) should be connected. An analog input option [1] or
[2] cannot be selected if the analog input is already in use as a reference source (selected in par.
F-01 Frequency Setting 1, par. C-30 Frequency Command 2 or par. C-34 Frequency Command 3).
Function:
The function selected in par. H-80 Function at Stop is active in the delay period.
Enter the time delay required before commencing acceleration.
Function:
Select the inverter switching frequency. Changing the switching frequency can help to reduce acoustic
noise from the motor.
NB!
Switching frequencies higher than 5.0 kHz lead to automatic derating of the maximum output of the
frequency converter.
AF-600 FP High Power Operating Instructions