GE AF-600 FP Operating Instructions Manual page 158

Fan and pump drive (460v/575v 150hp and above)
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

Mains Supply 3 x 525- 600 VAC
Max. input current
8
156
Typical Shaft output at 550 V
[kW]
Typical Shaft output at 575 V
[HP]
Unit Size IP21
Unit Size IP54
Unit Size IP00
Output current
Continuous
(at 550 V) [A]
Intermittent (60 sec over-
load)
(at 550 V) [A]
Continuous
(at 575 V) [A]
Intermittent (60 sec over-
load)
(at 575 V) [A]
Continuous KVA
(at 550 V) [KVA]
Continuous KVA
(at 575 V) [KVA]
Continuous
(at 550 V ) [A]
Continuous
(at 575 V) [A]
Max. cable size, mains mo-
tor, load share and brake
2 x 70 (2 x 2/0)
2
[mm
(AWG)]
1
Max. external pre-fuses [A]
Estimated power loss
at rated max. load [W]
4)
Weight,
Unit Size IP21, IP 54 [kg]
Weight,
Unit Size IP00 [kg]
Efficiency
4)
Output frequency
Heatsink overtemp. trip
Power card ambient trip
AF-600 FP High Power Operating Instructions
P110
P132
110
132
150
200
41
41
41
41
43
43
162
201
178
221
155
192
171
211
154
191
154
191
158
198
151
189
2 x 70 (2 x 2/0)
315
350
3114
3612
96
104
82
91
0.98
0 - 600 Hz
85 °C
90 °C
60 °C
P160
P200
160
200
250
300
42
42
42
42
44
44
253
303
278
333
242
290
266
319
241
289
241
289
245
299
234
286
2 x 185 (2 x 350 mcm) 2 x 185 (2 x 350 mcm)
350
400
4292
5156
125
136
112
123
110 °C
110 °C

Hide quick links:

Advertisement

Table of Contents
loading