3.1.12 Fuses

Branch circuit protection:

In order to protect the installation against electrical and fire hazard, all branch circuits in an installation, switch gear, machines etc., must be short-circuited and
over-current protected according to national/international regulations.

Short-circuit protection:

The frequency converter must be protected against short-circuit to avoid electrical or fire hazard. GE recommends using the fuses mentioned below to protect
service personnel and equipment in case of an internal failure in the drive. The frequency converter provides full short-circuit protection in case of a short-circuit
3
on the motor output.
Over-current protection
Provide overload protection to avoid fire hazard due to overheating of the cables in the installation. Fuses or circuit breakers can be used to provide the over-
current protection in the installation. Over-current protection must always be carried out according to national regulations.

3.1.13 Fuse tables

380-480 V, frame sizes 4X, 5X and 6X
The fuses below are suitable for use on a circuit capable of delivering 100,000 Arms (symmetrical), 480V/600V depending on the drive voltage rating. With the
proper fusing the drive Short Circuit Current Rating (SCCR) is 100,000 Arms.
Bussmann
AF-600
E1958
FP
JFHR2**
150 HP
FWH-
300
200 HP
FWH-
350
250 HP
FWH-
400
300 HP
FWH-
500
350 HP
FWH-
600
Table 3.3: For Unit Sizes 41, 42, 43, and 44,380-480 V
AF-600 FP
Bussmann PN*
450 HP
170M4017
500 HP
170M6013
550 HP
170M6013
600 HP
170M6013
Table 3.4: For Unit Sizes 51 and 52, 380-480 V
AF-600 FP
650 HP
750 HP
900 HP
1000 HP
1200 HP
1350 HP
Table 3.5: Unit Sizes 61, 62, 63, and 64, 380-480 V
AF-600 FP
650 HP
750 HP
900 HP
1000 HP
1200 HP
1350 HP
Table 3.6: Unit Sizes 61, 62, 63, and 64, Inverter module DC Link Fuses, 380-480 V
*170M fuses from Bussmann shown use the -/80 visual indicator, -TN/80 Type T, -/110 or TN/110 Type T indicator fuses of the same size and amperage may be
substituted for external use
**Any minimum 480 V UL listed fuse with associated current rating may be used to meet UL requirements.
24
Bussmann
SIBA
E4273
E180276
T/JDDZ**
RKI/JDDZ
JJS-
2028220-
300
315
JJS-
206xx32-
350
315
JJS-
206xx32-
400
400
JJS-
206xx32-
500
500
JJS-
206xx32-
600
600
Rating
700 A, 700 V
900 A, 700 V
900 A, 700 V
900 A, 700 V
Bussmann PN*
Rating
170M7081
1600 A, 700 V
170M7081
1600 A, 700 V
170M7082
2000 A, 700 V
170M7082
2000 A, 700 V
170M7083
2500 A, 700 V
170M7083
2500 A, 700 V
Bussmann PN*
170M8611
170M8611
170M6467
170M6467
170M8611
170M6467
AF-600 FP High Power Operating Instructions
Ferraz-
LittelFuse
Bussmann
Shawmut
E71611
E4274
E60314
JFHR2**
H/JDDZ**
JFHR2**
L50S-300
A50-P300
NOS-
L50S-350
A50-P350
NOS-
L50S-400
A50-P400
NOS-
L50S-500
A50-P500
NOS-
L50S-600
A50-P600
NOS-
Ferraz
6.9URD31D08A0700
6.9URD33D08A0900
6.9URD33D08A0900
6.9URD33D08A0900
Siba
20 695 32.1600
20 695 32.1600
20 695 32.2000
20 695 32.2000
20 695 32.2500
20 695 32.2500
Rating
1100 A, 1000 V
1100 A, 1000 V
1400 A, 700 V
1400 A, 700 V
1100 A, 1000 V
1400 A, 700 V
Bussmann
Internal
E125085
Option
JFHR2*
Bussmann
170M3017
170M3018
300
170M3018
170M3018
350
170M4012
170M4016
400
170M4014
170M4016
500
170M4016
170M4016
600
Siba
20 610 32.700
20 630 32.900
20 630 32.900
20 630 32.900
Internal Bussmann Option
170M7082
170M7082
170M7082
170M7082
170M7083
170M7083
Siba
20 781 32.1000
20 781 32.1000
20 681 32.1400
20 681 32.1400
20 781 32.1000
20 681 32.1400

Hide quick links: