Cooling And Airflow; Installation On The Wall - Ip21 (Nema 1) And Ip54 (Nema 12) Units; Duct Cooling; Back Cooling - GE AF-600 FP Operating Instructions Manual

Fan and pump drive (460v/575v 150hp and above)
Hide thumbs Also See for AF-600 FP:
Table of Contents

Advertisement

5.3.6 Cooling and Airflow

Cooling
Cooling can be obtained in different ways, by using the cooling ducts in the bottom and the top of the unit, by taking air in and out the back of the unit or by
combining the cooling possibilities.

Duct cooling

A dedicated option has been developed to optimize installation of IP00/chassis drive types in Rittal TS8 Units utilizing the fan of the frequency converter for forced
air cooling of the backchannel. Please consult GE for more details.
The air out the top of the Unit could but ducted outside a facility so the heat loses from the backchannel are not dissipated within the control room reducing air-
conditioning requirements of the facility.
Please contact GE for more information.

Back cooling

The backchannel air can also be ventilated in and out the back of a Rittal TS8 Unit. This offers a solution where the backchannel could take air from outside the
facility and return the heat loses outside the facility thus reducing air-conditioning requirements.
5
NB!
A doorfan(s) is required on the Rittal cabinet to remove the loses not contained in the backchannel of the drive. The minimum doorfan(s) airflow required at the
drive maximum ambient for the 43 and 44 is 391 m^3/h (230 cfm). The minimum doorfan(s) airflow required at the drive maximum ambient for the 52 is 782
m^3/h (460 cfm). If the ambient is below maximum or if additional components, heat loses, are added within the Unit a calculation must be made to ensure the
proper airflow is provided to cool the inside of the Rittal Unit.
Airflow
The necessary airflow over the heat sink must be secured. The flow rate is shown below.
Unit Size protection
IP21 / NEMA 1
IP54 / NEMA 12
IP21 / NEMA 1
IP54 / NEMA 12
IP00 / Chassis
* Airflow per fan. Unit Sizes 5X contain multiple fans.
Table 5.2: Heatsink Air Flow

5.3.7 Installation on the Wall - IP21 (NEMA 1) and IP54 (NEMA 12) Units

This only applies to 41 and 42 Unit Sizes (460V, 125 - 300 HP, 575/600V, 125 - 400 HP). It must be considered where to install the unit.
Take the relevant points into consideration before you select the final installation site:
Free space for cooling
Access to open the door
Cable entry from the bottom
Mark the mounting holes carefully using the mounting template on the wall and drill the holes as indicated. Ensure proper distance to the floor and the ceiling for
cooling. A minimum of 225 mm (8.9 inch) below the frequency converter is needed. Mount the bolts at the bottom and lift the frequency converter up on the bolts.
Tilt the frequency converter against the wall and mount the upper bolts. Tighten all four bolts to secure the frequency converter against the wall.
60
Unit Size
41 and 42
51
61, 62, 63 and 64
61, 62, 63 and 64
43 and 44
52
AF-600 FP High Power Operating Instructions
Door fan / Top fan airflow
170 m
3
/h (100 cfm)
340 m
3
/h (200 cfm)
700 m
3
/h (412 cfm)*
525 m
3
/h (309 cfm)*
255 m
3
/h (150 cfm)
255 m
3
/h (150 cfm)
Airflow over heatsink
765 m
3
/h (450 cfm)
1444 m
3
/h (850 cfm)
985 m
3
/h (580 cfm)
985 m
3
/h (580 cfm)
765 m
3
/h (450 cfm)
1444 m
3
/h (850 cfm)

Hide quick links: