Siemens SICAM Q80 System Manual page 48

Power quality recorder
Hide thumbs Also See for SICAM Q80:

Advertisement

48
SICAM Q80 7KG8080
The following settings are available for the averaging duration:
Period (for a period's duration)
10/12 Cycles (10 periods at 50 Hz or 12 periods at 60 Hz)
1 second values (corresponding to the values of the online monitoring)
mean (10 min mean values or corresponding to the
Note
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
Depending on the configuration (Y- or Delta-), only the particular variables which are
available are monitored. Any other events not available due to the configuration are ignored,
without any error message being posted. For this reason, templates can be re-used even if
the configuration is changed.
The shorter the averaging, the more events to be expected.
Events
Mean value recording
57
set)