The following value limits apply to the total overview:
Type
Frequency
Flicker
Events
Voltage differences
Asymmetry
THD
Harmonics
1) Up to this line, the measurement values are within the tolerance range.
2) Display of the values from the standard EN 50160.
3) Values lie far beyond accepted tolerances.
Evaluation: By default, the analysis is carried out for the entire measurement, and other time spans are available as
alternative selections.
On the basis of a particular measurement, the analysis can be carried out over different timeframes and with different
limits.
Standard: Since different limit data sets besides EN 50160 can be defined, it's possible to evaluate a measurement
according to a variety of requirements and to save the results for subsequent comparisons.
Case 1 - Measurement L-N (4 wire system), no converter
The device is able to measure up to 1000 V
Case 2 - Measurement L-L (3 wire-system) with converter in a 20 KV
operating voltage
converter: 20kV primary voltage, 100 V secondary voltage
1,2
Tolerance line
-1 % .. +1 %
-12 % > f > +8 %
1.0
U_RMS < ± 10.0 %
U_RMS > ± 50.0 %
3.0 %
8.0 %
0.5 % .. 6.0 %
Measurement time frame
Operation modes and settings
3
Chaos line
Note
> 10,0
> 50 events
> 20.0 %
> 16.0 %
> 15.0 %
depending on the number of harmonics
Power Quality Recorder SICAM Q80 7KG8080, System manual
E50417-H1076-C420-A2, Release 12.01.2015
117