Examples Of Replacing Components - Siemens SINAMICS S120 Function Manual

Hide thumbs Also See for SINAMICS S120:
Table of Contents

Advertisement

Basic information about the drive system

12.7 Examples of replacing components

12.7
Examples of replacing components
Note
To ensure that the entire functionality of a firmware version can be used, it is recommended
that all the components in a drive line-up have the same firmware version.
Description
If the type of comparison is set to the highest setting, the following examples apply.
A distinction is made between the following scenarios:
● Component with a different order number
● Components with identical order number
For p9909 = 1, the serial number and the hardware version of the new replaced component
are automatically transferred from the actual topology into the target topology and then
saved in a non-volatile manner.
For p9909 = 0, serial numbers and hardware versions are not automatically transferred. In
this case, when the data in the electronic rating plate match, the transfer is realized using
p9904 = 1 or p9995 = 1.
For the components that have been replaced, the electronic rating plate must match as far
as the following data are concerned:
● Component type (e.g. "SMC20")
● Order No. (e.g. "6SL3055–0AA0–5Bxx")
Example: Replacing a component with a different order number
Precondition:
● The replaced component has a different order number
Table 12- 11 Example: Replacing a component with a different order number
598
– Topology comparison component replacement active (p9909 = 1)
– Topology comparison component replacement inactive (p9909 = 0)
Action
Switch off the power supply
Replace the defective
component and connect the
new one
Switch on the power supply
Reaction
Alarm A01420
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Remark
Drive functions