2.8

Suppression bandwidths and setpoint limits

Description
In the range 0 U/min to setpoint speed, a drive train (e.g. motor, coupling, shaft, machine)
can have one or more points of resonance, which can result in vibrations. The suppression
bandwidths can be used to prevent operation in the resonance frequency range.
The limit frequencies can be set via p1080[D] and p1082[D]. These limits can also be
changed during operation with the connectors p1085[C] and p1088[C].
Figure 2-7
Function diagrams (see SINAMICS S120/S150 List Manual)
● 1550 Setpoint channel
● 3050 Suppression bandwidth and speed limiting
Drive functions
Function Manual, (FH1), 10/2008, 6SL3097-2AB00-0BP5
Suppression bandwidths, setpoint limitation
Extended setpoint channel
2.8 Suppression bandwidths and setpoint limits
57