SIDOOR functions
3.3 Extended functions
3.3.9.2
Configuring the logic
The free function blocks are configured at the parameter level. The input of a function block
can be linked to any output by entering the output's Q number in the input's REF parameter.
The outputs' Q numbers can be found in Overview (Page 76).
The REF parameters can be found in Table 4-40 FBLOCK-REF parameters (Page 187).
Example logic
The following figure shows an example logic. In the example logic, the level-controlled
outputs of the digital inputs DI3 and DI2 and a 1 ("high") are linked via the FBLOCK "AND0"
with the FBLOCK "Fault acknowledgement".
Figure 3-9
Example logic