Connecting To Cc-Link Ie Field Network Communication Unit - Mitsubishi Electric GOT2000 Series Connection Manual

Graphic operation terminal
Hide thumbs Also See for GOT2000 Series:
Table of Contents

Advertisement

11.2 System Configuration
11.2.1

Connecting to CC-Link IE Field Network communication unit

PLC CPU
PLC
CC-Link IE Field
Network
Model name
communication
MELSEC iQ-R Series
RJ71GF11-T2
Motion controller CPU
RJ71EN71
(MELSEC iQ-R Series)
RD77GF4
C Controller module
RD77GF8
(MELSEC iQ-R Series)
RD77GF16
CNC C80
RD77GF32
CR800-R(R16RTCPU)
MELSEC iQ-F Series
FX5-CCLIEF
R04ENCPU
R08ENCPU
R16ENCPU
R32ENCPU
R120ENCPU
MELSEC-Q
(Universal model)
QJ71GF11-T2
Q170MCPU
C Controller module
QD77GF16
(Q Series)
CNC C70
MELSEC-QS
QS0J71GF11-T2
MELSEC-L
LJ71GF11-T2
CC-Link IE Field
Network head module
Ethernet adapter
module
*1
*2
*3
*4
*5
11 - 8
11.2 System Configuration
CC-Link IE
Field Network unit
Communicatio
n type
unit
*4
*4
*4
*4
-
CC-Link IE
Field Network
*3
-
-
The overall extension cable length and the length between stations vary depending on the connection method (line, star or ring),
the system configuration, etc.
For details, refer to the following manual.
CC-Link IE Field Network Master/Local Module User's Manual
Use hubs that satisfy the following conditions.
• Compliance with the IEEE802.3 (1000BASE-T)
• Supporting the auto MDI/MDI-X function
• Supporting the auto-negotiation function
• Switching hub (A repeater hub is not available.)
Recommended switching hub (Mitsubishi Electric products)
Industrial switching hub
For details, refer to the following manual.
CC-Link IE Field Network Master/Local Module User's Manual
When connecting to the QD77GF16, refer to the following manual.
MELSEC-Q QD77GF Simple Motion Module User's Manual
When connecting to the RD77GF4, RD77GF8, RD77GF16 and RD77GF32, refer to the following manual.
RD77GF Simple Motion Module User's Manual
GT25-W, GT2505-V does not support the option device.
Connection cable
Connection cable
*2
Cable model
distance
Ethernet cable that meets
the 1000BASE-T standard:
Category 5e or higher,
12100m
(double-shielded, STP)
straight cable.
Type
Communication driver
GOT
CC-Link IE Field Network
GOT
Max
*5
option device
*1
GT15-J71GF13-T2
Model name
NZ2EHG-T8
Number of
connectable
Model
equipment
120 GOTs

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents