■3. Ethernet parameter settings of FX3U-ENET-ADP
(1) Ethernet settings
Set the Ethernet parameter at [FX Parameter] on GX Works2.
To set FX3U-ENET-ADP, GX Works2 Ver.1.90U or later is required.
For details on the setting of FX3U-ENET-ADP, refer to the following manual.
IP Address
Open Settings
Communication Data Code
Disable direct connection to MELSOFT
Do not respond to search for CPU on network
*1
*2
(2) Open settings
Open System
5 - 86
5.4 PLC Side Setting
FX3U-ENET-ADP User's Manual
Item
Channel
Set a channel according to the installation position of FX3U-ENET-ADP on the CPU body.
The default value of IP address is 192.168.1.250. Set the IP address corresponding to the system configuration.
POINT
POINT
POINT
When changing Ethernet parameter
After writing Ethernet parameters to the PLC CPU, turn the PLC CPU OFF then back ON again.
Item
Protocol
Setting
*1
CH1 or CH2
*2
192.168.3.19
Refer to (2).
(Use default value.)
:Required
Setting
TCP
MELSOFT connection
Setting
(with GOT connected)
:Set if necessary
:Not required
Setting
(with GOT connected)