Installing The Router Module To The Ach550 Drive - ABB ACH550 Installation Manual

Bacnet/ip router module rbip-01
Table of Contents

Advertisement

16

Installing the router module to the ACH550 drive

This section describes the necessary steps to install the router
module to the drive.
WARNING! Before installation, switch off the drive power supply.
Wait at least five minutes to ensure that the capacitor bank of the
drive is discharged. Switch off all dangerous voltages connected
from external control circuits to the inputs and outputs of the drive.
Note: Do not connect the router module to the network before you
have commissioned the device!
1. Before installation, switch off the drive power supply for at least
5 minutes to discharge the capacitor bank of the drive. For
more information, refer to
Note: Do not connect the cable shield to the drive!
For example connections, see ACH550 BACnet Protocol Manual
(3AUA0000004591 [English]), chapter Installation, section
Hardware installation.
Connect the wires in the order listed in the table below.
RBIP-01 terminal
B (+)
A (-)
AGND
Installation of the module
Safety
instructions.
ACH550 terminal
29, B (+)
30, A (-)
31, AGND
2. To connect the
MS/TP cable to the
Embedded
Fieldbus (EFB)
connectors of the
drive, install the
MS/TP cable as
shown in the
figure.
Wire
orange
white
blue