Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Figure 16. WinG3 "Interlocking Combination" dialog box.
Name: Displayed in the WinG3 Tree and List views. Default is
"Interlocking Combination" that can be edited when wanted /
required. "Area-Point" will be added in the tree view. "Area-Point"
will be shown under "Zone-Address" in the list view.
The Available interlocking outputs list displays all the previous
programmed outputs, Type = "Interlocking".
The Available interlocking inputs list displays all the previous
programmed inputs, Type "Interlocking". Select one Output and one
Input. Press Select and the selected output and input will be shown in
the Selected output and Selected input field respectively.
It is possible to Delete an output / input (from the field).
Output parent: Shows where the selected output is situated, e.g.
Control unit 0.
Input parent:
Shows where the selected input is situated, e.g.
Control unit 0.
Area and Point: Each "Interlocking Combination" is presented as
Area-Point (compare with Zone-Address). Area numbers 1-999 are
possible and within each Area, Point numbers 1-99 are possible to use.
An Area can only be used in one c.i.e.
Text = User definable text message to be shown in the menu H9/C1.
Can be written in this field or in the "Texts" dialog box, see chapter
"Creating the alarm texts via WinG3", page 111.