Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Control unit outputs R0 & R1
Each control unit has two programmable relay outputs:
R0
Relay output, NO or NC contacts programmable
R1
Relay output, NO or NC contacts programmable
Connections and more information, see dwg. 512 G3 - 23.
8 relays expansion board 4581 Output 0 –
Output 7
Each 4581 board has eight programmable relay outputs:
Output 0
Relay output, NO or NC contacts programmable
Output 1
Relay output, NO or NC contacts programmable
Output 2
Relay output, NO or NC contacts programmable
Output 3
Relay output, NO or NC contacts programmable
Output 4
Relay output, NO or NC contacts programmable
Output 5
Relay output, NO or NC contacts programmable
Output 6
Relay output, NO or NC contacts programmable
Output 7
Relay output, NO or NC contacts programmable
Relay contact ratings: Max. 2A @ 30 V DC.
Connections and more information, see dwg. 512 G3 – 34.
Inputs and Outputs expansion board 4583
Output 0 & Output 1
Expansion
board
4583
57
(monitored)
voltage outputs:
Output 0
Supervised (monitored) voltage output, 24V DC
200 mA (Fuse F1).
Output 1
Supervised (monitored) voltage output, 24V DC
200 mA (Fuse F2).
Connections and more information, see drawing 512 G3 – 35, sheet 1.
See also chapter "Inputs and outputs expansion board 4583", page 30.
The 3361 unit's Outputs Re0 & Re1
Each 3361 unit has two programmable relay outputs:
Re0 Relay output, NO or NC contacts programmable
Re1 Relay output, NO or NC contacts programmable
Connections and more information, see dwg. 512 G3 – 36.
57
This is default, but via WinG3 it is possible to set each output individually
as not supervised (not monitored). A normally high output is not supervised.
See also chapter "Calibration of supervised outputs", page 108.
58
See chapter "Technical data", page 157, regarding system voltage.
has
two
programmable,
70
supervised
58
, max.
58