Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Default for all zones is no two zone dependence.
NOTE!
Normally, only conventional zones (i.e. zone line inputs with
conventional detectors) should be used for two-zone dependence.
For analog / addressable detectors the two-address (unit) dependence
should be used.
Ten (1-10) groups are available.
For each group, write the zone numbers for the two-zone dependent
zones (min. two zones!!!) in the white field/line. Use comma as
punctuation mark between the zone numbers.
NOTE!
Check so that two or more zones are programmed in each group. (A
single zone in a group will never be able to activate any fire alarm!)

Statistics (System information)

In this dialog box you can read the following information:
This is what has been programmed so far in the system.
information will be updated when units etc. are added or deleted.

Edit Alarm texts

The user definable alarm text for each alarm point can be created /
edited in the alarm point dialog box respectively or via the menu:
Systems | Edit Alarm texts. See Text editor, page 112.