9.4.5
9.4.6
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
(e.g. 1N4004) in parallel with the coil, like in the alarm devices, see
drawing 512 G3 - 23.

Boxes

3362 Waterproof box (IP66 / 67). A grey polycarbonate box with
ingress protection rating IP66 / 67. Four compression glands
are included for the cable entries. Dimensions (L x W x H):
175 x 125 x 75 mm. 3362 can be used for e.g.:
Addressable multipurpose I/O unit 3361
Addressable 2 voltage outputs unit 3364

Duct detector chambers

6377 Duct detector chamber UG-4.
ABS and the venturi pipe is made of aluminium. It is supplied
with four IP65 glands for cable entry. 6377 can be used in
conventional as well as analog fire alarm systems, depending on
the base and detector mounted inside the housing (base 2324 +
4352 or base 3312 F/FL + 4301). The venturi pipe is available
with or without a built-in fan and in three lengths (0.6, 1.5 &
2.8 m). The pipe can easily be shortened to suit the ventilation
duct. Mounting bracket and filters are also available. For more
information see Data sheet MEW01280.