Planning Instructions Fire alarm system EBL512 G3, V1.1.x

Programmable voltage outputs (S0-S3)

The 24 V DC outputs S0-S3 are supervised (monitored)
Connections according to dwg 512 G3 – 23. When all connections are
done a calibration has to be performed, see chapter "Calibration of
supervised outputs", page 110 and the EBL512 G3 Operating
Instructions MEW01163, chapter "Calibration of supervised outputs
(menu H5/A1)".
Each output has to be programmed (via WinG3) regarding:
 Type of output, i.e. output for Control, Alarm devices, etc.
 Logic, i.e. normally low (default) or normally high (24 V DC)
 Activation time and type (steady, pulse, delay, etc.).
 Control expression (one or more trigger conditions).
See also the WinG3 help and chapter "Programmable outputs", page
68.

Programmable relay outputs (R0-R1)

Connections according to dwg 512 G3 – 23.
Each output has to be programmed (via WinG3) regarding:
 Type of output, i.e. output for Control, Alarm devices, etc.
 Logic, i.e. normally open (NO) or normally closed (NC) contacts.
 Activation time and type (steady, pulse, delay, etc.).
 Control expression (one or more trigger conditions).
See also the WinG3 help and chapter "Programmable outputs", page
68.

Programmable inputs (I0-I3)

Connections according to dwg 512 G3 – 23.
Each input has to be programmed (via WinG3) regarding:
 Trigger condition (Triggered by).
 Logic, i.e. normally open (NO) or normally closed (NC) contacts.
 Additional information, depending on the selected trigger
condition (Fault no., Zone, Address, Fault message (Error text),
etc.)
Open = R > 2K. Closed 0 R < 2K.
An input has to be activated > 0.5 sec.
See also the WinG3 help and chapter "Programmable inputs", page
62.
5
The outputs are in WinG3 default set as supervised but via WinG3 it is
possible to set each output (S0-S3) individually to be not supervised.
6
A normally high output is not supervised.