Panasonic MEW01 351 Planning Manual page 118

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01351
Rev: -
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
Backup SSD: (When connected and logged on to an EBL512 G3.)
For backup (upload) of SSD from all the EBL512 G3 control units and
connected Display Units (e.g. ext. FBP).
Verify SSD: (When connected and logged on to an EBL512 G3.)
The SSD stored in an EBL512 G3 control unit is compared with the
SSD open in WinG3. If they are the same, the checksums should also
be the same.
Erase SSD: (When connected and logged on to an EBL512 G3.) The
SSD stored in an EBL512 G3 control unit will be erased.
Download software: (When connected and not logged on to an
EBL512 G3.) For download of S/W (+ S/W text file) to one EBL512
G3 control unit.
Download FBP/EPU/AAU software: (When connected to a Display
Unit.) For download of S/W (+ S/W text file) to one Display unit.
Options: WinG3 settings.
Advanced functions: Can be one of three alternatives:
No Level selected: Alarm algorithm parameters cannot be changed.
Level 1 selected: All alarm algorithm parameters except the fire alarm
parameters can be changed.
Level 2 selected (which require a special password):
algorithm parameters can be changed. The convention for the open
installation can be changed.