20.2.5
Planning Instructions Fire alarm system EBL512 G3, V1.1.x
In the list (to the left), Steady (continuously) and Intermittent 0.8 /
0.8 s are already defined since these alternatives are often used. It is
however, possible to define them to something else.
User defined 1-8 have to be defined individually:
Name: Normally changed to something that describes the output
signal (e.g. "Steady") or what it is meant for (e.g. "Alarm devices").
Type: Steady / continuous (default)
Intermittent
Pulse
Steady, delayed activation
Intermittent, delayed activation
Pulse, delayed activation
Steady, delayed de-activation.
Depending on the selected type, one or more of the following fields
might have to be filled-in.
Delay time: Can be set to 0-255 sec.
Pulse length: Can be set to 0-255 sec.
Pulse off: Can be set to 0-255 sec.
De-activation: Can be set to 0-255 sec.