Panasonic MEW01091 Operating Instructions Manual page 17

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Rev: 3
Push buttons on the Fire Brigade Panel (FBP)
Push button
P1
Alarms queued (black)
P2
Silence buzzer
(yellow)
P3
Silence Alarm devices
5
(red)
P4
Reset (green)
P5
Evacuate (green)
Alert Annunciation
Acknowledge (green)
Disable (yellow)
Operation/function
Used, when LEDs "Alarms queued" (L2) are lit, to
scroll/browse through the queued alarms (zones).
Used to silence the buzzer in EBL128
Used to silence the sounders (i.e. to "reset" outputs for alarm
6
devices).
Used to reset the fire alarm(s).
sec.
8
Used to activate all the sounders (i.e. the outputs for alarm
devices).
Used to acknowledge an Alert Annunciation alarm.
9
10
Used to disables all zones in alarm state.
5
In the New Zealand convention = The "inside switch".
6
Via Win128 can be set if the alarm devices shall be continuous off /
disabled or re-sound for a new alarm.
7
Multiple reset (Default): All fire alarms will be reset simultaneously.
Single encapsulated reset: The fire alarm displayed in the LCD (first row to
the left) will be reset. When more than one fire alarm is activated (LEDs
"Alarms queued" are lit) each fire alarm has to be individually reset. The
encapsulation function is described in chapter "Single encapsulated reset",
page 50.
NOTE (1)! When "Multiple reset" is used, encapsulated reset can be done
by pressing "Reset" (P4) and 0.1 sec. later also press "Alarms queued" (P1)
and hold them pressed for > 0.5 sec. The fire alarm displayed in the LCD
(first row to the left) will be encapsulated or the points in alarm status within
one zone will be encapsulated or the whole zone (conventional) will be
encapsulated.
NOTE (2)! When "Single encapsulated reset" is used, you can make a
"Multiple reset" by pressing "Reset" (P4) and 0.1 sec. later also press "A" (in
the keypad) and hold them pressed for > 0.5 sec.
8
"Evacuate" is only valid in the "Belgian" and "Ukrainian" conventions.
9
"Alert Annunciation Acknowledge" is only valid in the "Czech", Bulgarian
and "Polish" conventions.
10
"Disable" is only valid in the "Australian" and New Zealand conventions.
15
EBL128 Operating Instructions V1.1.x
7
Has to be pressed for > 0.5