Re-enable output (B7)

Not available for users with access level / type "Information only".
Disabled outputs are listed in menu H4/U1.
If there is nothing to re-enable, --- List is empty --- will be
shown.
Log in with a User name and Password for typ Building officer (or
Service personnel), see page 5.
H1 Perform monthly test
Scroll (or press "2") to menu H2.
H2 Disable or re-enable
Press "A" to sub menu B1.
B1 Disable zone
Scroll (or press "7") to menu B7.
B7 Re-enable output
Press "A".
Only disabled "types" will be shown. Use the keypad to select "type"
of output:
0=Loop unit (3361, 3364, 3377/4477, 3379, 4380 or 4383) output.
1=C.i.e. output S0 or S1. (Default programmed as type "Alarm
device", i.e. cannot be individually disabled.)
2=C.i.e. output R0. (Default programmed as type "Routing
equipment" – Fire brigade tx, i.e. can in that case also be disabled via
menu B10.)
3=C.i.e. expansion board (4581 or 4583) output.
Press "A". L=This is a list in which you can scroll. Select the output
to re-enable press "A".
When required, re-enable more outputs or press "Return" (P9) until
menu B7 is shown.
Scroll to another menu or press "Return" to menu H2. Scroll to
another menu or leave the menu system by pressing "Return".
EBL128 version 2.0.x, Daily user's manual