Disconnect / Re-Connect Com Loop (H5/A1) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
Action
"Access"
"A"
E.g. "0", "A"
Rev: 3

Disconnect / Re-connect COM loop (H5/A1)

To avoid damage on the units and EBL128 during physical connection
/ disconnection of loop units, it is highly recommended to have the
loop disconnected (disabled), i.e. the loop is voltage free (dead).
Disconnected (disabled) loop is indicated by LED "Disablements" and
is listed in menu H4/U1.
NOTE! When you disconnect and re-connect the COM loop, all the
statistics shown in menu H5/A8 will be erased and set to "0".
Text in display
Disconnect / Re-connect COM loop
Disconnect (=0) or Re-connect (=1)
COM loop? 1
Disconnect / Re-connect COM loop
EBL128 Operating Instructions V1.1.x
ACCEPT? A1
ACCEPT?
ACCEPT? A1
105
Comments
According to chapter
"Access code for service
and maintenance", see
page 104.
Scroll or press "Return" to
H5. Scroll or press
"Return" to log off.