Re-Enable Interlocking Output (H9/C5) - Panasonic MEW01091 Operating Instructions Manual

Fire alarm system
Table of Contents

Advertisement

Panasonic Electric Works Nordic AB
MEW01091
32.5
Action
"Access"
Scroll to menu H9.
"A"
Scroll to menu C5.
"A"
"A"
or
"Return"
Rev: 3

Re-enable interlocking output (H9/C5)

Disabled interlocking outputs are listed in menu H4/U1.
Interlocking outputs (Type = Interlocking) will be re-enabled via this
menu but not via menu H2/B7.
If "00/00" is entered, all interlocking outputs, disabled via "00/00" in
menu H9/C4, will be re-enabled at the same time.
Text in display
Interlocking outputs and inputs
Activated interlocking outputs/inputs
Re-enable interlocking output
Re-enable interlocking output
area 00 point 00
Re-enable interlocking output
EBL128 Operating Instructions V1.1.x
ACCEPT? H9
ACCEPT? C1
ACCEPT? C5
ACCEPT?
ACCEPT? C5
131
Comments
According to chapter
"Access", see page 78.
This is a list in which you
can scroll. If there are no
disabled outputs, menu C5
will be shown again.
Press "A" (for re-enable)
or "Return" (not re-enable)
to menu C5.
Scroll or press "Return" to
menu H9. Scroll or press
"Return" to log off.