several minutes, wait a while before performing operation. The data backed up the
previous time and subsequently is lost. After recovery, check the data.
T-(
"Can not control this transmission adaptor." message was displayed by the browser.
Cause
The system entered a state in which it cannot control operation because the name
master data was not received.
Countermeasure
Wait until the Service Tool automatically acquires each name master data, and then
scan by detailed information scanning setting. For details, refer to "3-2-( Scanning".
T-(
"No data existing." message was displayed by the browser.
Cause
Data cannot be displayed because the unit data which is the display objective was
not received.
Countermeasure
Wait until the Service Tool automatically acquires each unit data, and then set
Intensive Data Acquisition (IDA) Mode at the system detail screen. For details, refer
to "(-6-1 Name and function of each area".
T-6
"Server access error occurred." message was displayed by the browser.
Cause
Error was generated when accessing the database.
The database may have been stopped by some cause.
The database may have been destroyed.
PC memory is used up.
Countermeasure
Close the browser and redo from login.
Restart the PC and then restart the Service Tool.
The database backed up last time is automatically restored. This software
cannot be used until completion of restore processing. Since restore process-
ing takes several minutes, wait a while before performing operation. The data
backed up the previous time and subsequently is lost. After recovery, check the
data.
Close all applications and stop unnecessary services of the PC in order to free
memory. Add extra memory if possible (refer "3-2 Recommended specs" of Set-
ting Manual).