Cable Specifications; Torque Specification - ABB 2 Series Operation And Installation Manual

Table of Contents

Advertisement

Technical data

10.2 Cable specifications

EVSE
AC Input
AC cable cross section
AC connection type
AC cable diameter (cable entry plate)
Protective Earth (PE)
PE cable cross section
PE connection type
PE cable diameter (cable entry plate)
PE connection point
Ethernet
CAT
Ethernet cable diameter (cable entry plate)
Tilt sensor (option)
Number of wires
Max. Wires cross section
Diameter outside
Conductor
Insultation
Voltage rating

10.3 Torque specification

EVSE
Parameter
Fasteners for the PE wire
Fasteners for the L1, L2, L3 (neutral wire Terra 60)
Fasteners for the connection of the EVSE to the base
(M12 bolt)
Tilt sensor screw terminal block
Terra 60
150 mm
2
(recommend)
M10 cable lug
27...35 mm
At least half of the phase cable cross section
M10 cable lug
19...28 mm
2 on the PE busbar
CAT 5e (recommend)
CAT 6 (high presence of electromagnetic
interference and/or noise)
8...13 mm
4 (2 wires for power supply and 2 wires for relay
contacts)
4mm
Cable diameter accepted by cable gland:
19...28 mm
Fine strand copper wire
PVC or other material that is serviceable for
outdoor use and UV-protected
600 V
Terra 60
Specification [Nm]
50...55
30...44
10
3
73
Terra 360
2 x 240 mm
2
(recommend)
M12 cable lug
Max. 34 mm
27...35 mm
19...28 mm
2
Terra 360
Specification [Nm]
50...75