Transmission Line - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

WIRING RULES
In the following cases, Signal Amplifier is required.
1) When the total length of the transmission line exceeded 500 m.
AB+BC+BD+DE+EF > 500 m (Fig. 1)
2) When the total number of units *1 is over 64.
Transmission line length between each unit*1 : MAX 400 m.
Total transmission line length: MAX 3600 m
AB+BC+BD+DE+EF+EG+GH < 3600 m (Fig. 2)
Terminal
resistor
Outdoor unit
B
A
D
Indoor unit
When AB+BC+BD+DE+EF>500m
:Signal Amplifier is required.
*1: Refer detail Meaning of unit on 1-2 VRF NETWORK SYSTEM.
Fig. 1

Transmission line

System
C
Controller
E
F
Touch
Panel
Controller
- (06 - 50) -
Fig. 2
Terminal
resistor
Outdoor unit
A
Transmission line
B
D
Terminal resistor
E
G
NS 3
Signal Amplifier
Indoor unit
NS 1
Touch
C
Panel
Controller
NS 2
F
System
Controller
NS 4
H