Features Of Control System - Fujitsu AIRSTAGE J-II Design & Technical Manual

Hide thumbs Also See for AIRSTAGE J-II:
Table of Contents

Advertisement

1-4.

FEATURES OF CONTROL SYSTEM

SIMPLE WIRING SYSTEM
1 transmission line can interlink all equipment regardless refrigerant circuit.
Non polar 2-conductor transmission cable.
Central control equipment can be connected anywhere on the transmission line, with no need
to bring from the outdoor unit.
„ - Making up the network system easily.
„ - Saving the total wiring length.
„ - Preventing incorrect connection.
„ - Saving installation time.
ADOPTION TO LARGE SCALE BUILDINGS
1 VRF network system allows to form large scale application as follows:
„ - Total transmission wiring length can be extended up to 3,600 m with signal amplifier unit.
„ - Indoor units can be connected up to 400.
„ - Outdoor units can be connected up to 100.
„ - Touch Panel Controller can be covered to control whole equipment centrally.
„ - By using multiple Touch Panel Controllers, control by individual zone or floor is possible
for convenient usage in various building applications.
„ - By adopting a separate interface, it is possible to connect other products and systems by
FUJITSU GENERAL such as Single type models (excluding some models), J series or
Multi air conditioner for buildings (e.g. Big multi). (Refer to 3-1. NETWORK CONVERTOR.)
System Controller allows to control up to 4 VRF network systems (Max. 1600 indoor units),
suitable for huge scale application.
RELIABILITY AND EASY MAINTENANCE
Stand-alone transmission network, allows each equipment to operate individually, thus failure
of the units does not affect other indoor units operation.
When a failure occurs, the error code is displayed on the individual controller and central
controller excepting Wireless Remote Controller.
Also error histories can memorized by each individual controller and central controller
excepting Wireless Remote Controller.
System Controller and Web Monitoring Tool allow to monitor operation status in real time via
Internet, and enable quick diagnoses.
Maintenance work is improved efficiency, because Service Tool can be connected to
anywhere on the transmission line.
- (05 - 10) -

Advertisement

Table of Contents
loading

Table of Contents