2-6.

HIGH STATIC PRESSURE DUCT TYPE

Model name
Power source
Available voltage range
Cooling
Capacity
Heating
Input power
Static pressure range
Standard static pressure
Airflow rate
Fan
Type x Quantity
Motor output
High
Sound pressure
Med
level
Low
Length
Fin pitch
Rows x Stages
Face Area
Heat exchanger
Pipe type (Material)
Fin
Model name
Air filter (Option)
Type
Net material
Material
Enclosure
Colour
Net
Dimensions
(H x W x D)
Gross
Net
Weight
Gross
Liquid
Connection
Gas
pipe diameter
Drain hose
NOTE: ARXC60, ARXC72, and ARXC90 can not be connected in J-II Series and J-IIS Series.
Note : Specifications are based on the following conditions.
Cooling : Indoor temperature of 27°CDB / 19°CWB, and outdoor temperature of 35°CDB / 24°CWB.
Heating : Indoor temperature of 20°CDB / (15°CWB), and outdoor temperature of 7°CDB / 6°CWB.
Pipe length : 7.5 m; Height difference between outdoor unit and indoor unit : 0 m.
ARXC36GBTH ARXC45GATH ARXC60GATH ARXC72GBTH ARXC90GBTH
11.2
kW
12.5
W
207
Pa
0 to 200
Pa
100
1,990
High
(553)
3
m
/ h
1,680
Med
(l / s)
(467)
1,330
Low
(369)
W
197
42
dB(A)
36
32
mm
2
m
Type (Material)
Surface
treatment
mm
40
kg
45
mm
- (04 - 20) -
230 V ~, 50Hz
198 to 264 V
12.5
18.0
14.0
20.0
715
730
100 to 250
100 to 250
100
100
3,500
3,500
(972)
(972)
3,000
3,000
(833)
(833)
2,460
2,460
(683)
(683)
Sirocco × 2
540
49
49
45
45
42
42
890
1.30
4 × 16
0.30
Grooved H-pin (Copper)
Slit(Aluminium)
Hydrophilic coating
UTD-LF60KA
Fungicide type
PP honeycomb
galvanized sheet iron
-
400 × 1,050 × 500
460 × 1,230 × 640
46
51
ø 9.52(Flare)
ø 19.05 (Flare)
VP25 [ø 25(I.D.) ; ø 32(O.D.)]
22.4
25.0
25.0
28.0
681
819
0 to 300
0 to 300
150
150
3,900
4,300
(1,083)
(1,195)
3,300
4,000
(917)
(1,111)
3,000
3,500
(833)
(972)
700 x 2
47
48
43
46
40
44
1,250
1.45
4 × 18
0.50
-
450 × 1,587 × 700
520 × 1,750 × 825
84
100
ø 12.70 (Brazing)
ø 22.22 (Brazing)

Advertisement