4.3 Inverter

The following chapter only deals with the connection with inverters of the 800 series.
Depending on the inverter type, the permissible address range of the variables that can be
read via SLMP is different. This quick start guide only provides an overview using examples;
details about the individual parameters and registers can be found in the corresponding
manuals for the Mitsubishi Electric Inverter.
What they have in common, however, are the settings of the inverter parameters for
Ethernet communication.
IP Address
The IP address of the inverter must be in the same network area as the control level (CH2)
of the IoT gateway. In the quickstart example this area is at "192.168.0.xx", the inverter gets
the address "2" for the A800/F800 Inverter and "11" for the E800 through the corresponding
entries in parameters 1434 to 1437.
Other communication settings may have to be carried out, such as adapting the subnet
mask (parameters 1438 to 1441).
For all other settings, please refer to the corresponding inverter manuals.
SLMP Connection
The communication between the IoT gateway and the inverter takes place via SLMP TCP /
IP. To do this, the value 5012 or 5013 must be entered in one of the inverter parameters
1427 to 1429.
In the example, parameter 1428 is set.
_________________________________________________________________________
Document: Quickstart_IoTGateway_EN
Mitsubishi Electric Europe B.V.
Rev: 001G
Date: 01/02/2022